Alternator 55KVA, 380V, 50Hz, 1500 RPM. Datang dari PT. Lautan Berkah Internasional — equipment milik PT. Sagatrade Murni. Kondisinya: stator winding terbakar. Insulation resistance di bawah threshold. Bearing housing out of tolerance. Commutator rusak.
Tiga minggu kemudian, hasilnya: Insulation 16.42 GΩ. Winding resistance seimbang. Running test OK. Berikut report lengkapnya.
📋 Equipment Information
| Customer | PT. Lautan Berkah Internasional (PT. Sagatrade Murni) |
| Equipment | Alternator |
| Manufacturer | Leroy Somer |
| Rating | 55 KVA |
| Voltage | 380V |
| Frequency | 50 Hz |
| RPM | 1500 RPM |
| Work Order | 031/SB-LBI/II/26 & 031/SO-LBI/II/26 |
| Inspection Date | 5 Februari 2026 |
| Completion Date | 17 Februari 2026 |
| Salesman | Pungkas Fitriadi |
| Prepared by | Rida Yunitha |
🔍 Kondisi Awal — As Received (5 Februari 2026)
Saat diterima di workshop UNO Solusi Teknik, alternator ini sudah menunjukkan gejala kerusakan yang jelas. Inspection sesuai EASA AR100-2020 dan IEEE 43-2013 dilakukan segera.
🔴 Insulation Resistance — AS RECEIVED
| Phase | Value | Status |
|---|---|---|
| U - G | 41.8 MΩ | ✅ Acceptable |
| V - G | 26.3 KΩ | ❌ CRITICAL |
| W - G | 1.467 MΩ | ❌ FAIL |
Test Voltage: 500 VDC | Reference minimum: 100 MΩ
🔴 Generator Stator Winding Resistance — AS RECEIVED
| Phase | Resistance | Status |
|---|---|---|
| U1 - U2 | 78.87 KΩ | ❌ Tidak seimbang |
| V1 - V2 | 130.81 KΩ | ❌ Tidak seimbang |
| W1 - W2 | 83.80 KΩ | ❌ Tidak seimbang |
🔴 Field Winding — Inter-Pole Resistance (AS RECEIVED)
| Pole | Resistance | Status |
|---|---|---|
| Pole 1 | 2.2 Ω | ✅ Balanced |
| Pole 2 | 2.2 Ω | ✅ Balanced |
| Pole 3 | 2.2 Ω | ✅ Balanced |
| Pole 4 | 2.2 Ω | ✅ Balanced |
⚠️ Inspection Findings
- Generator Stator Winding Terbakar — Burnout confirmed, discolorations pada copper winding
- Commutator Winding — Severe bar laminated akibat hard carbon brush scratch
- Rotor Bars — Fit in laminated core iron — GOOD CONDITION
- Bearing Journal DE & NDE — Good condition (per EASA AR100)
- Bearing Housing DE & NDE — OUT OF TOLERANCE
- Polarization Index (PI) — 1.2 (Reference min: 2) — MARGINAL
- Bearing DE — Perlu replacement: 6310-2Z
- Bearing NDE — Perlu replacement: 6210-2Z
📐 Bearing Clearance — AS RECEIVED
| Position | Journal Shaft Ø | Housing Bearing Ø | Clearance | Status |
|---|---|---|---|---|
| DE Journal | 105.018 mm | 225.010 mm | — | Out of Tolerance |
| NDE Journal | 100.018 mm | 180.010 mm | — | Out of Tolerance |
🔧 Work Scope & Repair Process
Berdasarkan inspection findings, berikut work scope yang disepakati:
Work Scope (By UNO Solusi Teknik):
- Undercut Commutator Stator — Perbaikan commutator yang severe laminated
- Replace Bearing DE & NDE — 6310-2Z (DE) & 6210-2Z (NDE)
- Metal Spray Bearing Housing DE & NDE — Additional work untuk restore housing ke toleransi
- Stator Rewinding — Cleaning, drying out, re-varnish, winding ulang
- Rotor Assembly & Balancing — Rotor assembly setelah stator rewinding
- No-Load Running Test — Monitoring electric parameters dan temperature
- Cleaning & Painting — Exterior restoration
Standard yang dipakai: EASA AR100-2020, IEEE 43-2013, IEC 60034-1
✅ Hasil Akhir — Final Report (17 Februari 2026)
Setelah seluruh proses selesai, final inspection dilakukan pada 17 Februari 2026. Hasilnya — transformasi total.
🟢 Insulation Resistance — FINAL
| Phase | Before | After | Status |
|---|---|---|---|
| U - G | 41.8 MΩ | 16.42 GΩ | ✅ Excellent |
| V - G | 26.3 KΩ | 14.25 GΩ | ✅ Excellent |
| W - G | 1.467 MΩ | 12.03 GΩ | ✅ Excellent |
Test Voltage: 500 VDC | Improvement: from 1.467 MΩ → 16.42 GΩ = x11,200x increase
🟢 Generator Stator Winding Resistance — FINAL
| Phase | Before | After | Status |
|---|---|---|---|
| U1 - U2 | 78.87 KΩ | 41.62 mΩ | ✅ Balanced |
| V1 - V2 | 130.81 KΩ | 41.81 mΩ | ✅ Balanced |
| W1 - W2 | 83.80 KΩ | 41.72 mΩ | ✅ Balanced |
All phases within ±5% — Perfect balance. Winding resistance konsisten di ~41.7 mΩ per phase.
📊 Before vs After Summary
| Parameter | Before | After | Change |
|---|---|---|---|
| Insulation U-G | 41.8 MΩ | 16.42 GΩ | 🟢 +390x |
| Insulation V-G | 26.3 KΩ | 14.25 GΩ | 🟢 +540,000x |
| Insulation W-G | 1.467 MΩ | 12.03 GΩ | 🟢 +8,200x |
| Stator Resistance U | 78.87 KΩ | 41.62 mΩ | 🟢 Normalized |
| Stator Resistance V | 130.81 KΩ | 41.81 mΩ | 🟢 Normalized |
| Stator Resistance W | 83.80 KΩ | 41.72 mΩ | 🟢 Normalized |
| Bearing DE | Needs Replacement | 6310-2Z Installed | 🟢 Replaced |
| Bearing NDE | Needs Replacement | 6210-2Z Installed | 🟢 Replaced |
| Bearing Housing | Out of Tolerance | Metal Spray Restore | 🟢 Restored |
| Commutator | Severe Laminated | Undercut & Refurbished | 🟢 Restored |
| Polarization Index | 1.2 (Marginal) | >4 (Excellent) | 🟢 Fixed |
👷 Tim Teknisi
| Inspected by | Rian Pamungkas |
| Checked by | Dadeng Sobandi |
| Approved by | Handry Naufal |
| Work Order | 031/SB-LBI/II/26 & 031/SO-LBI/II/26 |
| Report Date | 17 Februari 2026 |
| Revision | 00 |
📅 Maintenance Recommendation
| Item | Interval |
|---|---|
| General External Condition | 3 years |
| Winding and Rotor Condition | 4–6 years |
| Vibration Measurement | 1 month |
| Insulation Resistance / PI | 2–4 years |
| Bearing Insulation | 2–4 years |
| Bearing Lubrication | As specified |
| Rolling Bearing Replacement | 4–6 years |
Rewinding, repair, dan maintenance alternator — mulai dari 5KVA sampai 5000KVA. Alat test lengkap: insulation tester, winding tester, balancer, surge tester, no-load test rig.